DOC PREVIEW
Chapter_9

This preview shows page 1-2-24-25 out of 25 pages.

Save
View full document
View full document
Premium Document
Do you want full access? Go Premium and unlock all 25 pages.
Access to all documents
Download any document
Ad free experience
View full document
Premium Document
Do you want full access? Go Premium and unlock all 25 pages.
Access to all documents
Download any document
Ad free experience
View full document
Premium Document
Do you want full access? Go Premium and unlock all 25 pages.
Access to all documents
Download any document
Ad free experience
View full document
Premium Document
Do you want full access? Go Premium and unlock all 25 pages.
Access to all documents
Download any document
Ad free experience
Premium Document
Do you want full access? Go Premium and unlock all 25 pages.
Access to all documents
Download any document
Ad free experience

Unformatted text preview:

1Chapter 9Control System InstrumentationFigure 9.3 A typical process transducer.Transducers and Transmitters• Figure 9.3 illustrates the general configuration of a measurement transducer; it typically consists of a sensing element combined with a driving element (transmitter).2Chapter 9• Transducers for process measurements convert the magnitude of a process variable (e.g., flow rate, pressure, temperature, level, or concentration) into a signal that can be sent directly to thecontroller. • The sensing element is required to convert the measured quantity, that is, the process variable, into some quantity moreappropriate for mechanical or electrical processing within the transducer.Standard Instrumentation Signal Levels• Before 1960, instrumentation in the process industries utilized pneumatic (air pressure) signals to transmit measurement and control information almost exclusively.• These devices make use of mechanical force-balance elements to generate signals in the range of 3 to 15 psig, an industry standard.3Chapter 9• Since about 1960, electronic instrumentation has come into widespread use. SensorsThe book briefly discusses commonly used sensors for the most important process variables. (See text.)Transmitters• A transmitter usually converts the sensor output to a signal level appropriate for input to a controller, such as 4 to 20 mA.• Transmitters are generally designed to be direct acting. • In addition, most commercial transmitters have an adjustable input range (or span).• For example, a temperature transmitter might be adjusted so thatthe input range of a platinum resistance element (the sensor) is50 to 150 °C.4Chapter 9• In this case, the following correspondence is obtained:20 mA150 °C4 mA50 °COutputInput• This instrument (transducer) has a lower limit or zero of 50 °C and a range or span of 100 °C.• For the temperature transmitter discussed above, the relation between transducer output and input is()()()20 mA 4 mAmA 50 C 4 mA150 C 50 CmA0.16 C 4 mACmTTT−=−+−=−DDDDD5Chapter 9The gain of the measurement element Kmis 0.16 mA/°C. For any linear instrument:range of instrument output(9-1)range of instrument inputmK =Final Control Elements• Every process control loop contains a final control element (actuator), the device that enables a process variable to be manipulated.• For most chemical and petroleum processes, the final control elements (usually control valves) adjust the flow rates of materials, and indirectly, the rates of energy transfer to and from the process.6Chapter 9Figure 9.4 A linear instrument calibration showing its zero and span.7Chapter 9Control Valves• There are many different ways to manipulate the flows of material and energy into and out of a process; for example, the speed of a pump drive, screw conveyer, or blower can be adjusted.• However, a simple and widely used method of accomplishing this result with fluids is to use a control valve, also called an automatic control valve.• The control valve components include the valve body, trim, seat, and actuator.Air-to-Open vs. Air-to-Close Control Valves• Normally, the choice of A-O or A-C valve is based on safety considerations.8Chapter 9Figure 9.7 A pneumatic control valve (air-to-open).9Chapter 9• We choose the way the valve should operate (full flow or no flow) in case of a transmitter failure. • Hence, A-C and A-O valves often are referred to as fail-openand fail-closed, respectively.Example 9.1Pneumatic control valves are to be specified for the applications listed below. State whether an A-O or A-C valve should be used for the following manipulated variables and give reason(s).a) Steam pressure in a reactor heating coil.b) Flow rate of reactants into a polymerization reactor.c) Flow of effluent from a wastewater treatment holding tank into a river.d) Flow of cooling water to a distillation condenser.10Chapter 9Valve PositionersPneumatic control valves can be equipped with a valve positioner, a type of mechanical or digital feedback controller that senses the actual stem position, compares it to the desiredposition, and adjusts the air pressure to the valve accordingly.Specifying and Sizing Control ValvesA design equation used for sizing control valves relates valve lift to the actual flow rate q by means of the valve coefficient Cv, the proportionality factor that depends predominantly on valve size or capacity:A()(9-2)vvsPqCfg∆= A11Chapter 9• Here q is the flow rate, is the flow characteristic, is the pressure drop across the valve, and gsis the specific gravity of the fluid.• This relation is valid for nonflashing fluids.• Specification of the valve size is dependent on the so-called valve characteristic f. • Three control valve characteristics are mainly used.• For a fixed pressure drop across the valve, the flow characteristic is related to the lift , that is, the extent of valve opening, by one of the following relations:()f AvP∆()01ff≤≤()01≤≤AA1Linear:Quick opening: (9-3)Equal percentage:fffR−===AAA12Chapter 9Figure 9.8 Control valve characteristics.13Chapter 9where R is a valve design parameter that is usually in the range of 20 to 50.RangeabilityThe rangeability of a control valve is defined as the ratio of maximum to minimum input signal level. For control valves, rangeability translates to the need to operate the valve within the range 0.05 ≤ f ≤ 0.95 or a rangeability of 0.95/0.05 = 19.To Select an Equal Percentage Valve:a) Plot the pump characteristic curve and , the system pressure drop curve without the valve, as shown in Fig. 9.10. The difference between these two curves is . The pump should be sized to obtain the desired value of , for example, 25 to 33%, at the design flow rate qd.sP∆vP∆/vsPP∆∆14Chapter 9Figure 9.10 Calculation of the valve pressure drop from the pump characteristic curve and the system pressure drop without the valve ()vP∆().sP∆15Chapter 9b) Calculate the valve’s rated Cv, the value that yields at least 100% of qdwith the available pressure drop at that higher flow rate.c) Compute q as a function of using Eq. 9-2, the rated Cv, and from (a). A plot of the valve characteristic (q vs. ) should be reasonably linear in the operating region of interest (at least around the design flow rate). If it is not suitably linear, adjust


Chapter_9

Download Chapter_9
Our administrator received your request to download this document. We will send you the file to your email shortly.
Loading Unlocking...
Login

Join to view Chapter_9 and access 3M+ class-specific study document.

or
We will never post anything without your permission.
Don't have an account?
Sign Up

Join to view Chapter_9 2 2 and access 3M+ class-specific study document.

or

By creating an account you agree to our Privacy Policy and Terms Of Use

Already a member?